logo
0%
...

Products

UL5128 FIRE-RESISTANCE MICA HIGH TEMPERATURE WIRE

Home / Fire Resistant MGT Wire (mica tape wrapped) / UL5128 FIRE-RESISTANCE MICA HIGH TEMPERATURE WIRE

+1 (551) 216-4118

UL5128 FIRE-RESISTANCE MICA HIGH TEMPERATURE WIRE

Technical Parameters

  • Type: AWM5128
  • Conductor:nickel plated copper or nickel
  • Rated Temperature:-60℃∽+450℃
  • Rated Voltage:300V
  • Color: yellow
  • Application: widely used in thermalelectrity, petrol, electromechanical equipment, power plant, drying room, heating light sources, thermalelectrity equipment etc. high temperature working environments

AWG

Conductor

No./Dia.

(mm)

Avg. Insulation Thickness

(mm)

Overall

Dia.

(mm)

Max. Resistance

20℃ (≤Ω/km)

20

7/0.30

0.56

2.1±0.3

37.4

18

11/0.30

0.56

2.3±0.3

23.5

17

14/0.30

0.56

2.4±0.3

18.5

16

18/0.30

0.56

2.6±0.3

14.6

15

21/0.30

0.56

2.7±0.3

11.5

14

28/0.30

0.56

3.0±0.3

9.15

13

35/0.30

0.56

3.2±0.3

7.26

12

49/0.30

0.56

3.8±0.3

5.75

11

56/0.30

0.89

4.6±0.5

4.48

10

77/0.30

0.89

5.2±0.5

3.55

8

112/0.30

0.89

6.0±0.5

2.23

7

140/0.30

0.89

6.3±0.5

1.76

6

190/0.30

0.89

7.3±0.5

1.41

5

228/0.30

0.89

7.8±0.5

1.11

4

304/0.30

0.89

8.8±0.5

0.882

Remarks: more AWG available, pls. contact us for more information